Products

team

BKLiYCY/EB

böhm Kabel
Data Cables

APPLICATION:

For hazardous areas. Cables with special marking (blue). Usable as flexible control and measuring cables to meet the requirements for the installation of electrical apparatus. These installations are not earthed and require a separate power circuit. Not suitable for laying below ground. The braided copper screen ensures the transmission of data signals and is free from interference. Extensively oil-resistant.

Technical data

  • adapted to DIN VDE 0165 part 1, EN 60079-14, IEC 60079-14 sect. 12.2.2.6

Temperature range

  • flexing -5° C to +80° C
  • fixed installation -30° C to +80° C

Operational Voltage

  • 350 V (not for purposes of high current and power installation) for 0,34 mm²

Nominal voltage

  • U0/U = 300/500 V

Test voltage

  • 2000 V

Insulation resistance

  • min. 20 MOhm x km